CHP - Power on!

The CHP is connected via circuit breaker to the main bus bar.

If several modules are connected, we recommend a sub-distribution. It is however possible to put them seperately on the main bus bar. Conductor cross-section and size of fuse depend on quantity and type of the CHP modules. The ASV 21/46 requires a conductor cross-section of at least 16 mm² and a fuse protection of 3 * 40 A NH 00.

These information for download (PDF document) (- KB)

 